SIZING OF OXIDATION POND FOR SMALL TOWN IN HAITI
Load: 100,000 gallons/day Conversion to SI units: 100,000 gallons/day × 3.785 liters/gallon = 378,500 liters/day = 4.3 liters/sec = 0.0043 m3/sec Design load: 0.005 m3/sec Hydraulic residence time (for more than 70% BOD removal): 20 days Required volume of pond: 0.005 m3/s × 20 days × 86,400 sec/day = 8,640 m3 Design depth = 1.2 m. Design area = 8,640 m3 / 1.2 m = 7,200 m2 Pond of rectangular dimensions: Length L = 100 m; Width W = 72 m. Pond of square dimensions: Length L = 85 m; Width W = 85 m. Mean January temperature: 20oC (assumed) Minimum BOD removal: 76% Effluent treated to close to secondary standard.